Mx2000 Three-Phase Delta Ac Power Distribution Module Electrical Specifications - Juniper MX2010 Hardware Manual

Universal routing platform
Hide thumbs Also See for MX2010:
Table of Contents

Advertisement

NOTE:
Additional grounding is provided to an AC-powered router when you plug its PDMs into
grounded AC power receptacles.
WARNING:
protective earthing terminal (Metric [–M6] and Standard [–¼-20] screw ground lugs)
provided on the chassis in addition to the grounding pin of the power supply cord. This
separate protective earth terminal must be permanently connected to earth.
RELATED DOCUMENTATION
Grounding an MX2000 Router | 289
Tools and Parts Required for Connecting an MX2000 Router to Power | 219
MX2000 Three-Phase Delta AC Power Distribution Module Electrical
Specifications
Table 59 on page 178
lists the three-phase delta AC power distribution monitor (PDM) electrical
specifications.
Table 59: Three-Phase Delta AC Power Distribution Module Electrical Specifications
Item
AC input voltage
AC input line frequency
AC input current rating
AC system input power
Efficiency
The router is installed in a restricted-access location. It has a separate
Specification
Operating range: 200–240 VAC (line-to-line) (nominal)
50/60 Hz (nominal)
50 A @ 200 VAC (input #1 for each PDM)
25 A @ 200 VAC (input #2 for each PDM)
16800 W (input #1), 8400 W (input #2)
90.5% at 50% load and 220 VAC IN
178

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents