Connecting Power To A Dc-Powered Mx2000 Router With Dc Power Distribution Modules; China) - Juniper MX2010 Hardware Manual

Universal routing platform
Hide thumbs Also See for MX2010:
Table of Contents

Advertisement

Connecting Power to a DC-Powered MX2000 Router with DC Power
Distribution Modules (240 V China)
WARNING:
from the DC circuit. To ensure that all power is OFF, locate the circuit breaker on the
panel board that services the DC circuit, switch the circuit breaker to the OFF position,
and tape the switch handle of the circuit breaker in the OFF position.
You connect DC (240 V China) power to the router by attaching power cables from the external DC power
sources to the DC power cable that is connected to the PDM. The power cables are orderable
(CBL-PWR-240V-CH).
To connect the DC (240 V China) source power cables (CBL-PWR-240V-CH) to the router:
1. Switch off the dedicated customer site circuit breakers. Ensure that the voltage across the DC power
source cable leads is 0 V and that there is no chance that the cable leads might become active during
installation.
2. Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect the strap to
one of the ESD points on the chassis.
NOTE:
If the DC PSMs (240 V China) are installed in the router, make sure the power
switches on all PSMs are turned to the off (O) position.
3. Plug the power cord into the power sockets on the DC PDM (240 V China). Refer to Figure 1. Apply
slight pressure so that the power cord is firmly seated in the power socket until you feel it engage. As
you plug in each power cord, the power LED for the socket lights up green.
Before performing DC power procedures, ensure that power is removed
309