Ptx5000 Three-Phase Delta Ac Power Distribution Unit Specifications; Ptx5000 Three-Phase Wye Ac Power Distribution Unit Specifications; Table 55: Three-Phase Delta Ac Pdu Electrical Specifications; Table 56: Three-Phase Wye Ac Pdu Electrical Specifications - Juniper PTX5000 Hardware Manual

Packet transport router
Hide thumbs Also See for PTX5000:
Table of Contents

Advertisement

PTX5000 Packet Transport Router Hardware Guide
Related
Documentation

PTX5000 Three-Phase Delta AC Power Distribution Unit Specifications

Table 55: Three-Phase Delta AC PDU Electrical Specifications

Item
Maximum output power
AC input voltage
AC input line frequency
AC input current rating
Maximum AC input
Related
Documentation

PTX5000 Three-Phase Wye AC Power Distribution Unit Specifications

Table 56: Three-Phase Wye AC PDU Electrical Specifications

Item
Maximum output power
AC input voltage
AC input line frequency
AC input current rating
130
Understanding Normal-Capacity Power System Power Zones on page 71
PTX5000 AC Power System Description on page 42
PTX5000 AC Power Electrical Safety Guidelines on page 612
Table 55 on page 130
lists the AC power distribution unit (PDU) electrical specifications.
Specification
17,600 W
Operating range: 200 through 240 VAC (line-to-line) (nominal)
50/60 Hz (nominal)
40 A @ 240 VAC (line-to-line)
48 A @ 200 VAC (line-to-line)
16,600 W
Connecting Power to the PTX5000 Three-Phase Delta AC PDUs on page 210
PTX5000 AC Power Electrical Safety Guidelines on page 612
PTX5000 AC Power Cord Specifications on page 132
Table 56 on page 130
lists the AC power distribution unit (PDU) electrical specifications.
Specification
17,600 W
Operating range: 200 through 240 VAC (line-to-neutral) (nominal)
Operating range: 346 through 415 VAC (line-to-line) (nominal)
50Hz/60Hz (nominal)
25 A @ 240 VAC (line-to-neutral)
30 A @ 200 VAC (line-to-neutral)
Copyright © 2017, Juniper Networks, Inc.