Omron NX701-17 Series Troubleshooting Manual page 86

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

3 Error Tables
Event code
Event name
34010000 hex
I/O Setting
Check Error
44400000 hex
PLC Function
Processing
Error
64010000 hex
Impossible to
Access Spe-
cial Unit
102D 0000
CJ-series
hex (Ver. 1.03
Unit Backup
or later)
Failed
102E0000 hex
CJ-series
(Ver. 1.03 or
Unit Restore
later)
Operation
Failed
30200000 hex
Unsupported
(Ver. 1.02 or
Unit Setting
later)
80010000 hex
Illegal Packet
Discarded
3-8
Meaning
Assumed cause
There is an incon-
• A Unit model or Special Unit
sistency between a
unit number in the Unit Configu-
Unit model in the
ration in the CPU Unit is differ-
Unit Configuration
ent from the Unit model or the
in the CPU Unit and
Special Unit unit number of the
the Unit model that
Unit that is mounted in the Con-
is mounted in the
troller.
Controller.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
An error occurred in
• The setting of the rotary
data exchange
switches or a DIP switch pin on
between the CPU
a Special Unit is not correct.
Unit and a Special
• An error occurred in the Special
Unit.
Unit.
• The Unit connection is faulty.
• Noise
• A Unit has failed.
The backup opera-
• An error occurred in the Unit
tion for a CJ-series
Configuration.
Unit ended in an
• An error occurred for a Special
error.
Unit.
• A restart is in progress for the
Special Unit.
• A Unit model or Special Unit
unit number in the Unit Configu-
ration in the CPU Unit is differ-
ent from the Unit model or the
Special Unit unit number of the
Unit that is mounted in the Con-
troller.
• The CPU Unit or CJ-series Unit
has failed.
The restore opera-
• An error occurred in the Unit
tion for a CJ-series
Configuration.
Unit ended in an
• An error occurred for a Special
error.
Unit.
• The Unit Configuration in the
backup file does not agree with
the physical Unit configuration.
• A restart is in progress for the
Special Unit.
• The restore conditions that are
required by the Special Unit are
not met.
• The backup files are corrupted.
• The CPU Unit or CJ-series Unit
has failed.
A setting in the
• A setting in the Special Unit is
Special Unit is not
not supported by the CPU Unit.
supported.
An illegal packet
• Noise
was received
during message
communications.
The illegal packet
was discarded.
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
S
NJ/NX-series Troubleshooting Manual (W503)
Reference
W500
W500
W500
W500
W500
W500
W500

Advertisement