Omron NX701-17 Series Troubleshooting Manual page 247

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

Event code
Event name
00200000 hex
Non-volatile
Memory
Hardware
Error
10410000 hex
Control
Parameter
Error in Mas-
ter
35100000 hex
External
Input Setting
Error
35110000 hex
SSI Data Set-
ting Error
40200000 hex
NX Unit Pro-
cessing Error
743D0000 hex
Incorrect
Synchroniza-
tion Com-
mand
NJ/NX-series Troubleshooting Manual (W503)
Meaning
Assumed cause
An error occurred in
• Non-volatile memory failure
non-volatile mem-
ory.
An error occurred in
For the NX bus of CPU Units
the control parame-
• The power supply to the CPU
ters that are saved
Unit was turned OFF while writ-
in the master.
ing the Unit operation settings
was in progress. Or there is an
error in the area of the non-vol-
atile memory in the CPU Unit in
which the Unit operation set-
tings for the relevant NX Unit
are saved.
For Communications Coupler
Units
• The power supply to the Com-
munications Coupler Unit was
turned OFF while writing the
Unit operation settings was in
progress. Or there is an error in
the area of the non-volatile
memory in the Communications
Coupler Unit in which the Unit
operation settings for the rele-
vant NX Unit are saved.
A setting for an
• The same function (other than
external input is not
a general-purpose input) is
correct.
assigned to more than one of
the external inputs (I0 to I2).
There is an error in
• The sum of the values set for
the SSI data set-
the Valid Data Length and the
tings.
Leading Bits parameters
exceeds 32.
• The sum of the values set for
the Multi-turn Data Length, Sin-
gle-turn Data Length, and the
Status Data Length parameters
exceeds 32.
• The sum of the value set for the
start bit position and the data
length of the SSI data exceeds
the value set for the Valid Data
Length parameter.
• The value set for the Encoder
Resolution parameter exceeds
the range expressed by the
data length set for the Single-
turn Data Length parameter.
A fatal error
• An error occurred in the soft-
occurred in an NX
ware.
Unit.
Updating the target
• The communications cable that
position data in the
connects the Communications
synchronization
Coupler Unit is disconnected or
refresh failed con-
a connection is faulty.
secutively for more
• Noise
than the specified
number of times.
3 Error Tables
Level
Maj
Prt
Min
Obs Info
S
W524
S
W524
S
W524
S
W524
S
W524
S
U
W524
Reference
3
3-169

Advertisement

Table of Contents
loading

Table of Contents