Event code
Event name
18230000 hex
Absolute
Encoder
Multi-rotation
Counter Error
24680000 hex
Motor Non-
conformity
24690000 hex
Motor Non-
conformity
246A0000 hex
Motor Non-
conformity
246B0000 hex
Motor Non-
conformity
246C0000 hex
Motor Non-
conformity
28010000 hex
Motor Set-
ting Error
28020000 hex
Motor Combi-
nation Error 1
28030000 hex
Motor Combi-
nation Error 2
34E10000 hex
Servo Drive
Overheat
NJ/NX-series Troubleshooting Manual (W503)
Meaning
Assumed cause
The encoder
• Servomotor failed.
detected a multi-
rotation counter
error.
The Servo Drive
• The Servo Drive and Servomo-
and Servomotor
tor combination is not correct.
combination is not
correct.
The Servo Drive
• The Servo Drive and Servomo-
and Servomotor
tor combination is not correct.
combination is not
correct.
The Servo Drive
• The Servo Drive and Servomo-
and Servomotor
tor combination is not correct.
combination is not
correct.
The Servo Drive
• The Servo Drive and Servomo-
and Servomotor
tor combination is not correct.
combination is not
correct.
The Servo Drive
• The Servo Drive and Servomo-
and Servomotor
tor combination is not correct.
combination is not
correct.
Settings associ-
• Settings associated with the
ated with the motor
motor and external encoder are
and external
missing.
encoder are miss-
ing.
The value set for
• The Motor Rated Rms Cur-
the motor current
rent/Motor Peak Absolute Cur-
exceeds the maxi-
rent exceeds the maximum
mum motor capac-
motor capacity allowed for the
ity allowed for the
Servo Drive.
Servo Drive.
The value set for
• The Motor Rated Rms Current
the motor exceeds
is too low compared with the
the drive range of
maximum motor capacity of the
the motor.
Servo Drive.
• The percentage of the Motor
Coil Unit Mass to the Motor
Rated Force is too high.
• The automatically adjusted Cur-
rent Loop Proportional
Gain/Current Loop Integral
Gain is too high.
• The percentage of the Motor
Peak Absolute Current to the
Motor Rated Rms Current is
greater than 500%.
The temperature of
• The ambient temperature of the
the Servo Drive
Servo Drive exceeded the
radiator or power
specified value.
elements exceeded
• Overload
the specified value.
3 Error Tables
Level
Maj
Prt
Min
Obs Info
S
I576
S
I576
S
I576
S
I576
S
I576
S
I576
S
I577
S
I577
S
I577
S
I576, I577