Omron NX701-17 Series Troubleshooting Manual page 312

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

3 Error Tables
CJ-series DeviceNet Units
The section provides tables of the errors (events) that can occur in the following Units.
CJ1W-DRM21
The manual names are given below for the catalog numbers given in the Reference column of the
event table.
Cat. No.
W497
Event code
Event name
04880000 hex
Unit Memory
Error
04890000 hex
Network
Power Error
148D 0000 hex
Invalid Scan
List Data
148E0000 hex
Invalid Setup
Data
24480000 hex
Node
Address
Duplicated
Error
34BC0000 hex Routing
Table Error
3-234
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit
Meaning
Assumed cause
An error occurred
• There is a source of noise
when writing to
nearby.
internal memory
• Non-volatile memory failure
where the error his-
tory is saved.
Network power is
• Communications power is not
not being supplied.
being supplied normally from
the network.
There is an error in
• The power was interrupted
the contents of the
during writing the scan list to
slave scan list or
the non-volatile memory.
master scan list
stored in non-vola-
tile memory.
There is illegal data
• The power was interrupted
in the settings for
while the system was writing
the slave function.
the parameters.
• Non-volatile memory life
An error was dis-
• The node address of the Devi-
covered during the
ceNet Unit is also set for
node address dupli-
another node.
cation check when
starting the Devi-
ceNet Unit.
There is illegal data
• The local DeviceNet Unit is not
in the routing tables
in the routing tables.
set in the CPU Unit.
• The routing table format is
incorrect.
• Reading the routing tables
timed out.
Manual name
Level
Maj
Prt
Min
Obs Info
S
U
S
S
S
S
S
U
NJ/NX-series Troubleshooting Manual (W503)
Reference
W497
W497
W497
W497
W497
W497