Omron NX701-17 Series Troubleshooting Manual page 243

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

Event code
Event name
65110000 hex
Process
Value Over
Range
65120000 hex
Process
Value Under
Range
80220000 hex
NX Message
Communica-
tions Error
90400000 hex
Event Log
Cleared
 Heater Burnout Detection Units (NX-HB)
Event code
Event name
00200000 hex
Non-volatile
Memory Hard-
ware Error
05100000 hex
A/D Converter
Error
NJ/NX-series Troubleshooting Manual (W503)
Meaning
Assumed cause
The process tem-
• The sensor is disconnected.
perature exceeded
• The sensor or the compensat-
the upper limit of
ing cables are not wired cor-
temperature con-
rectly.
version range.
• The sensor and the input type
setting do not agree.
• The range of the input type is
too narrow for the temperatures
that need to be measured.
• An unused channel is not dis-
abled.
The process tem-
• The sensor or the compensat-
perature went
ing cables are not wired cor-
below the lower
rectly.
limit of temperature
• The sensor and the input type
conversion range.
setting do not agree.
• The range of the input type is
too narrow for the temperatures
that need to be measured.
An error was
For the NX bus of CPU Units
detected in mes-
• The message communications
sage communica-
load is high.
tions and the
For Communications Coupler
message frame
Units
was discarded.
• The message communications
load is high.
• The communications cable is
disconnected or broken.
• Message communications were
cutoff in communications.
The event log was
• The event log was cleared by
cleared.
the user.
Meaning
An error occurred in
• Non-volatile memory fail-
non-volatile memory.
An error occurred in
• Noise
the A/D converter
• A/D converter failure
Maj
Assumed cause
Maj
ure.
3 Error Tables
Level
Reference
Prt
Min
Obs Info
U
S
W566 (W522)
U
S
W566 (W522)
S
W566 (W522)
S
W566 (W522)
Level
Reference
Prt
Min
Obs
Info
S
W566
S
W566
3
3-165

Advertisement

Table of Contents
loading

Table of Contents