3 Error Tables
Event code
Event name
100A0000 hex
Data Not
(Ver. 1.10 or
Saved to Bat-
later)
tery-backup
Memory
100B0000 hex
Non-volatile
Memory Data
Corrupted
100C 0000 hex
Event Level
(Ver. 1.03 or
Setting Error
later)
100F0000 hex
Present Val-
(Ver. 1.13 or
ues of
later)
Retained
Variables
Restoration
Error
10100000 hex
Present Val-
(Ver. 1.13 or
ues of
later)
Retained
Variables Not
Saved
40010000 hex
PLC System
Processing
Error
40020000 hex
PLC System
Processing
Error
40030000 hex
PLC System
Processing
Error
40040000 hex
PLC System
(Ver. 1.10 or
Processing
later)
Error
40050000 hex
PLC System
(Ver. 1.10 or
Processing
later)
Error
3-4
Meaning
Assumed cause
An error occurred in
• An error occurred in the soft-
the software and
ware.
data could not be
saved in battery-
backup memory
during power-OFF
processing.
A file that must be
• The Controller power supply
in non-volatile
was turned OFF while the
memory is missing
BUSY indicator was lit.
or corrupted.
• The power supply to the Con-
troller was interrupted momen-
tarily while the BUSY indicator
was lit.
• The CPU Unit has failed.
The settings in the
• The event level settings are not
event level setting
correct because the power sup-
file are not correct.
ply to the Controller was inter-
rupted or communications with
the Sysmac Studio were dis-
connected during a download
of the event level settings.
• The event level settings are not
correct because the power sup-
ply to the Controller was inter-
rupted during a Clear All
Memory operation.
• Non-volatile memory failed.
An error occurred in
• An error occurred in the soft-
the software and
ware.
the present values
of retained vari-
ables could not be
restored at startup.
The values were
initialized.
A forced shutdown
• A forced shutdown is per-
is performed or an
formed.
error occurred in
(NY-series Controllers)
the software and
• An error occurred in the soft-
the present values
ware.
of retained vari-
ables could not be
saved during
power-OFF pro-
cessing.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
S
S
S
S
NJ/NX-series Troubleshooting Manual (W503)
Reference
W500, W535
W500, W535,
W578
W500, W535,
W578
W578
W578
W500
W500, W535,
W578
W500, W535,
W578
W535, W578
W535, W578

Advertisement