Omron NX701-17 Series Troubleshooting Manual page 291

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

Event code
Event name
74810000 hex
Command
Error
78010000 hex
Operation
Command
Competition
78020000 hex
Absolute
Encoder Sta-
tus Error
84B10000 hex
EtherCAT
State Change
Error
NJ/NX-series Troubleshooting Manual (W503)
Meaning
Assumed cause
A mistake was
• When bit 09 (Remote) of the
made in using a
Statusword (6041 hex) was set
command.
to 1 (remote), and the Servo
Drive was in operation enabled
state (Servo ON), a command
was received that changes the
communications state from
Operational to another state
(Init, Pre-operational, or Safe-
operational state).
• When bit 09 (Remote) of the
Statusword (6041 hex) was set
to 0 (local), a command was
received during FFT or test run
status that changes the ESM
state from Operational, Safe-
operational, or Pre-operational
state to Init state.
• An unsupported number was
set for 6060 hex (Operation
Mode).
• During Fully-closed Control
Mode, csv or cst was set for
6060 hex (Operation Mode)
(This applies to Cylinder-type
Servomotors.).
• The setting of 6060 hex (Oper-
ation Mode) was changed at an
interval of less than 2 ms.
• Homing was started when 6098
hex (Homing Method) was set
to a value other than 8, 12, 19,
20, 33, 34,or 35.
• Data setting warnings (B0 hex)
occurred continuously for the
number of data setting warn-
ings that is set in 3781 hex
(Data Setting Warning Detec-
tion Count).
An attempt was
• EtherCAT communications
made to establish
(change from Init to Pre-opera-
EtherCAT commu-
tional state) was established or
nications or to turn
an attempt to turn ON the Servo
ON the Servo from
from the Controller (enable
the Controller
operation) was made while exe-
(enable operation)
cuting an FFT that operates
while executing an
with the Servo Drive trial run.
FFT that operates
with the Servo
Drive alone or a
trial run.
The rotation of the
• The rotation of the encoder was
encoder was higher
higher than the specified value
than the specified
when the power supply was
value when the
turned ON.
power supply was
turned ON.
A communications
• A communications state
state change com-
change command was received
mand was received
for which the current communi-
for which the cur-
cations state could not be
rent communica-
changed.
tions state could not
be changed.
3 Error Tables
Level
Maj
Prt
Min
Obs Info
S
I576, I577
S
I576, I577
S
I576
S
I576, I577
Reference
3
3-213