Omron NX701-17 Series Troubleshooting Manual page 273

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

Event code
Event name
28080000 hex
Main Circuit
Power Sup-
ply Phase
Loss Error
280D0000 hex
Runaway
Detected
357D0000 hex
DC Setting
Error
357E0000 hex
Synchroniza-
tion Cycle
Setting Error
357F 0000 hex
Mailbox Set-
ting Error
35800000 hex
RxPDO Set-
ting Error
35810000 hex
TxPDO Set-
ting Error
35820000 hex
RxPDO Map-
ping Error
35830000 hex
TxPDO Map-
ping Error
35840000 hex
PDO WDT
Setting Error
35850000 hex
Node
Address
Updated
35860000 hex
SM Event
Mode Set-
ting Error
NJ/NX-series Troubleshooting Manual (W503)
Meaning
Assumed cause
The phase loss of
• Incorrect wiring, for example
the main circuit
the single-phase power supply
power supply
is input to a 3-phase input type
was detected.
Servo Drive
• In the case where the single-
phase power supply is input to
a single- and 3-phase input
type Servo Drive, the phase
loss detection is enabled.
• The power supply voltage is low
or insufficient
• Broken wiring of the main circuit
power supply input
• Servo Drive failure
The motor
There is incorrect wiring of
rotated in the
the motor cable or a broken
direction opposite
cable.
to the command.
The motor rotated in the
direction opposite to the com-
mand by external forces.
A mistake was
• A mistake was made in the DC
made in the DC
Mode operation setting
Mode operation
setting.
When the DC
• The variable PDO mapping is
mode was estab-
used, and the number of
lished, the cycle
objects is more than the maxi-
time was set to
mum number of mapped
the inoperable
objects for the cycle time
value.
• The cycle time setting is incor-
rect
An incorrect mail-
• An incorrect mailbox setting of
box setting of
Sync Manager was detected
Sync Manager
was detected.
An RxPDO set-
• The RxPDO setting of Ether-
ting error was
CAT master is incorrect
detected.
• Servo Drive failure
A TxPDO setting
• The TxPDO setting of Ether-
error was
CAT master is incorrect
detected.
• Servo Drive failure
An incorrect
• An incorrect RxPDO was set,
RxPDO was set.
such as out of the allowable
range of Index, Subindex, or
size
An incorrect
• An incorrect RxPDO was set,
TxPDO was set.
such as out of the allowable
range of Index, Subindex, or
size
An incorrect PDO
• An incorrect PDO WDT setting
WDT setting was
was detected
detected.
The node
• The node address is changed
address is
from a set value in Sysmac Stu-
changed to a
dio to a value of the ID switches
value of the ID
switches.
The unsupported
• The unsupported SM Event
SM Event Mode
Mode was set
was set.
3 Error Tables
Level
Maj
Prt
Min Obs Info
S
S
S
S
S
S
S
S
S
S
S
S
Refer-
ence
I586
I586
3
I586
I586
I586
I586
I586
I586
I586
I586
I586
I586
3-195