3 Error Tables
Event code
Event name
84600000 hex
Communica-
tions Error
84610000 hex
Repeater
Unit Commu-
nications
Error
64980000 hex
Representa-
tive Warning
64990000 hex
Representa-
tive Alarm
3-242
Meaning
Assumed cause
A Slave Unit was
• Cable lengths (trunk line and
disconnected from
branch lines) are unsuitable.
the network.
• A cable is disconnected or
loose.
• A terminating resistance is not
connected. Or, the terminating
resistance is somewhere other
than the end of the trunk line.
• Noise
• The Slave Unit does not
respond to communications
from the Master Unit because
the Slave Unit is faulty, the line
is disconnected, or the commu-
nications power supply is inter-
rupted.
An error occurred in
• Cable lengths (trunk line and
Repeater Unit com-
branch lines) are unsuitable.
munications.
• A cable is disconnected or
loose.
• A terminating resistance is not
connected. Or, the terminating
resistance is somewhere other
than the end of the trunk line.
• Noise
• The Repeater Unit does not
respond to communications
from the Master Unit because
the Repeater Unit is faulty, the
line is disconnected, or the
communications power is inter-
rupted.
A warning has
• A warning has occurred in at
occurred in at least
least one Slave Unit.
one Slave Unit.
An alarm has
• An alarm has occurred in at
occurred in at least
least one Slave Unit.
one Slave Unit.
Level
Maj
Prt
Min
Obs Info
S
U
S
U
S
S
NJ/NX-series Troubleshooting Manual (W503)
Reference
W493
W493
W493
W493