Event code
Event name
65230000 hex
Discrepancy
Error at
Safety Input
65240000 hex
Overload
Detected at
Test Output
65250000 hex
Stuck-at-high
Detected at
Test Output
65270000 hex
Short Circuit
Detected at
Safety Out-
put
65280000 hex
Stuck-at-high
Detected at
Safety Out-
put
80200000 hex
NX Unit I/O
Communica-
tions Error
NJ/NX-series Troubleshooting Manual (W503)
Meaning
Assumed cause
An error was
• There is a ground fault or dis-
detected in discrep-
connection in the input signal
ancy evaluation of
line.
safety input termi-
• The connected device is faulty.
nals.
• The setting of the discrepancy
time is not correct.
• Chattering occurred in the input
signal from the external input
device, such as a safety door.
An overcurrent was
• There is a ground fault on the
detected at the test
output signal line.
output terminal.
• The external device is faulty.
It was detected that
• The positive power supply line
the test output ter-
is in contact with the output sig-
minal is stuck ON.
nal line.
• The internal circuit is faulty.
• A memory error or signal error
occurred due to a transient
cause, such as a software error
or excessive noise.
A ground fault was
• There is a ground fault on the
detected on the
output signal line.
safety output termi-
nal.
It was detected that
• The positive power supply line
the safety output
is in contact with the output sig-
terminal is stuck
nal line.
ON.
• The output power supply is out-
side the specifications.
• The internal circuit is faulty.
• A memory error or signal error
occurred due to a transient
cause, such as a software error
or excessive noise.
An I/O communica-
• The NX Unit is not mounted
tions error occurred
properly.
between the Com-
• The power cable for the Unit
munications Cou-
power supply is disconnected.
pler Unit and the
Or, the wiring from the Unit
NX Unit.
power supply to the NX Units is
incorrect.
• The power cable for the Unit
power supply is broken.
• The voltage of the Unit power
supply is outside the specified
range. Or, the capacity of the
Unit power supply is insuffi-
cient.
• There is a hardware error in the
NX Unit.
3 Error Tables
Level
Maj
Prt
Min
Obs Info
S
Z930
S
Z930
S
Z930
S
Z930
S
Z930
S
Z930
Reference
3