Omron NX701-17 Series Troubleshooting Manual page 116

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

3 Error Tables
Event code
Event name
5401240B hex
Failed To Delete
(Ver. 1.08 or
Specified File
later)
5401240C hex
Specified File
(Ver. 1.08 or
Access Failed
later)
5401240D hex
IP Address Setting
(Ver. 1.10 or
Invalid
later)
54012C00 hex
NX Message Error
(Ver. 1.05 or
later)
54012C01 hex
NX Message
(Ver. 1.05 or
Resource Overflow
later)
54012C02 hex
NX Message Time-
(Ver. 1.05 or
out
later)
54012C03 hex
Incorrect NX Mes-
(Ver. 1.05 or
sage Length
later)
3-38
Meaning
A file was not deleted after
• The FTP client com-
it was transferred with an
FTP client communications
instruction.
• It was not possible to
An FTP transfer for an FTP
• The file specified for
client communications
instruction failed because
file access failed.
• The file or directory
Instruction execution was
• The network address
not possible because there
is an error between the IP
address setting of the port
specified in the instruction
and the other port settings.
• Both the port specified
An error response code
• Depends on the
was returned for an NX
message.
The maximum resources
• More than 32 NX mes-
that you can use for NX
message instructions at the
same time was exceeded.
A timeout occurred during
• The specified NX Unit
execution of an NX mes-
sage.
• The NX message was
• Power to the remote
• Communications are
• The communications
• The communications
• Noise
The length of the NX mes-
• The size that is speci-
sage is not correct.
Assumed cause
Maj
Prt
munications instruc-
tion was set to delete
files after they are
transferred, but it was
not possible to delete
the specified file
because it had a read-
only attribute.
delete the file speci-
fied for the FTP client
communications
instruction because it
was in use by another
application.
the FTP client commu-
nications instruction
was in use by another
application.
specified for the FTP
client communica-
tions instruction to
write is write pro-
tected.
of the port specified in
the instruction is the
same as the network
address of another
port.
in the instruction and
the other ports are set
as unused ports.
nature of the error.
sage instructions were
executed at the same
time.
does not exist.
closed because it
timed out.
Unit is OFF.
stopped at the remote
Unit.
cable connector is dis-
connected.
cable is broken.
fied for WriteDat or
Path is too long.
NJ/NX-series Troubleshooting Manual (W503)
Level
Refer-
ence
Min
Obs
Info
S
W502
S
W502
S
W502
S
W502
S
W502
S
W502
S
W502

Advertisement

Table of Contents
loading

Table of Contents