Instructions
A version in parentheses in the Event code column is the unit version of the CPU Unit when the event
code was added.
Event codes for instructions are supported by CPU Units with unit version 1.02 or later.
The manual names are given below for the catalog numbers given in the Reference column of the
event table.
Cat. No.
W502
Event code
Event name
54010400 hex
Input Value Out of
Range
54010401 hex
Input Mismatch
54010402 hex
Floating-point
Error
54010403 hex
BCD Error
54010404 hex
Signed BCD Error
NJ/NX-series Troubleshooting Manual (W503)
NJ/NX-series Instructions Reference Manual
Meaning
An input parameter for an
• An input parameter for
instruction exceeded the
valid range for an input
variable. Or, division by an
integer of 0 occurred in divi-
sion or remainder calcula-
tions.
The relationship for the
• The relationship for an
instruction input parame-
ters did not meet required
conditions. Or, a numeric
value during or after
• A value when pro-
instruction execution did
not meet conditions.
Non-numeric data was
• Non-numeric data was
input for a floating-point
number input parameter to
an instruction.
A value that was not BCD
• A hexadecimal digit of
was input for a BCD input
parameter to an instruction.
An illegal value was input
• An illegal value was
for the most significant digit
for a signed BCD input
parameter to an instruction.
Manual name
Assumed cause
Maj
Prt
an instruction
exceeded the valid
range for an input vari-
able. Or, division by an
integer of 0 occurred
in division or remain-
der calculations.
input parameter did
not meet required con-
ditions.
cessing an instruction
or in the result does
not meet the condi-
tions.
input for a floating-
point number input
parameter to an
instruction.
A, B, C, D, E, or F was
input for a BCD input
parameter to an
instruction.
input for the most sig-
nificant digit for a
signed BCD input
parameter to an
instruction.
• The most-signifi-
cant digit was 2 to F
when _BCD0 was
specified as the
BCD format.
• The most-signifi-
cant digit was A, B,
C, D, or E when
_BCD2 was speci-
fied as the BCD for-
mat.
• The most-signifi-
cant digit was B, C,
D, or E when
_BCD3 was speci-
fied as the BCD for-
mat.
3 Error Tables
Level
Refer-
ence
Min
Obs
Info
S
W502
S
W502
S
W502
S
W502
S
W502
3-25