Omron NX701-17 Series Troubleshooting Manual page 249

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

Event code
Event name
80200000 hex
NX Unit I/O
Communica-
tions Error
80210000 hex
NX Unit Out-
put Synchro-
nization Error
NJ/NX-series Troubleshooting Manual (W503)
Meaning
Assumed cause
An I/O communica-
For the NX bus of CPU Units
tions error occurred
• An error that prevents normal
in an NX Unit.
NX bus communications
occurred in a CPU Unit.
• An NX Unit is not mounted
properly.
• The power cable for the Unit
power supply is disconnected,
or the wiring from the Unit
power supply to the NX Units is
incorrect.
• The power cable for the Unit
power supply is broken.
• The voltage of the Unit power
supply is outside the specified
range, or the capacity of the
Unit power supply is insuffi-
cient.
• There is a hardware error in an
NX Unit.
For Communications Coupler
Units
• An error that prevents normal
NX bus communications
occurred in a Communications
Coupler Unit.
• The NX Unit is not mounted
properly.
• The power cable for the Unit
power supply is disconnected.
Or, the wiring from the Unit
power supply to the NX Units is
incorrect.
• The power cable for the Unit
power supply is broken.
• The voltage of the Unit power
supply is outside the specified
range. Or, the capacity of the
Unit power supply is insuffi-
cient.
• There is a hardware error in the
NX Unit.
An output synchro-
For the NX bus of CPU Units
nization error
• I/O refreshing on the NX bus is
occurred in the NX
not performed normally due to
Unit.
an error in the CPU Unit.
For Communications Coupler
Units
• The communications cable con-
nected to the Communications
Coupler Unit is broken or the
connection is faulty.
• The communications cable is
affected by noise.
3 Error Tables
Level
Maj
Prt
Min
Obs Info
S
W524
S
W524
Reference
3