Omron NX701-17 Series Troubleshooting Manual page 250

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

3 Error Tables
Event code
Event name
80240000 hex
NX Unit
Clock Not
Synchro-
nized Error
80220000 hex
NX Message
Communica-
tions Error
84D0 0000 hex
SSI Commu-
nications
Error
90400000 hex
Event Log
Cleared
3-172
Meaning
Assumed cause
A time information
For the NX bus of CPU Units
error occurred in an
• There is a hardware error in an
NX Unit.
NX Unit.
• There is a hardware error in a
CPU Unit.
For Communications Coupler
Units
• There is a hardware error in an
NX Unit.
• There is a hardware error in an
EtherCAT Coupler Unit.
An error was
For the NX bus of CPU Units
detected in mes-
• The message communications
sage communica-
load is high.
tions and the
For Communications Coupler
message frame
Units
was discarded.
• The message communications
load is high.
• The communications cable is
disconnected or broken.
• Message communications were
cutoff in communications.
An error occurred in
• The SSI data settings do not
SSI communica-
agree with the SSI communica-
tions.
tions settings in the connected
device.
• The wiring between the NX Unit
and the connected device is not
correct or disconnected.
• Noise
The event log was
• The event log was cleared by
cleared.
the user.
Level
Maj
Prt
Min
Obs Info
S
S
U
S
S
NJ/NX-series Troubleshooting Manual (W503)
Reference
W524
W524
W524
Same as
above.