3 Error Tables
Event code
Event name
35040000 hex
Mailbox Set-
ting Error
35050000 hex
RxPDO Set-
ting Error
35060000 hex
TxPDO Set-
ting Error
35070000 hex
PDO WDT
Setting Error
35080000 hex
SM Event
Mode Set-
ting Error
35090000 hex
TxPDO Map-
ping Error
350A0000 hex
RxPDO Map-
ping Error
350B0000 hex
Illegal State
Transition
Request
Received
350C 0000 hex
Error State
Transition
Received
350D 0000 hex
Synchroniza-
tion Cycle
Setting Error
40200000 hex
NX Unit Pro-
cessing Error
84C0 0000 hex
NX Unit
Communica-
tions Timeout
3-152
Meaning
Assumed cause
An incorrect mail-
• An incorrect mailbox setting
box setting was
was detected for the Sync Man-
detected for the
ager.
Sync Manager. (AL-
Status Code: 0016
hex)
An error was
• An error was detected in the
detected in the
RxPDO settings.
RxPDO settings.
(AL-Status Code:
001D hex)
An error was
• An error was detected in the
detected in the
TxPDO settings.
TxPDO settings.
(AL-Status Code:
001E hex)
An incorrect PDO
• An incorrect PDO WDT setting
WDT setting was
was detected.
detected. (AL-Sta-
tus Code: 001F
hex)
An SM Event Mode
• An SM Event Mode that is not
that is not sup-
supported was set.
ported was set.
(AL-Status Code:
0028 hex)
An incorrect TxPDO
• An incorrect TxPDO was set,
was set. (AL-Status
e.g., the index, subindex, or
Code: 0024 hex)
size was outside of the allow-
able range.
An incorrect
• An incorrect RxPDO was set,
RxPDO was set.
e.g., the index, subindex, or
(AL-Status Code:
size was outside of the allow-
0025 hex)
able range.
An incorrect state
• An incorrect state transition
transition request
request was received.
was received. (AL-
Status Code: 0011
hex)
An unclear state
• An unclear state transition
transition request
request was received.
was received. (AL-
Status Code: 0012
hex)
When DC Mode
• When DC Mode was confirmed,
was confirmed, the
the cycle time was set to a
cycle time was set
value that made operation
to a value that
impossible.
made operation
impossible. (AL-
Status Code: 0035
hex)
A fatal error
• An error occurred in the soft-
occurred in an NX
ware.
Unit.
An error occurred in
• An NX Unit is not mounted
I/O data communi-
properly.
cations with the NX
• An NX Unit has failed.
Units.
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
S
S
S
S
S
S
NJ/NX-series Troubleshooting Manual (W503)
Reference
W519
W519
W519
W519
W519
W519
W519
W519
W519
W519
W519
W519

Advertisement