Omron NX701-17 Series Troubleshooting Manual page 258

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

3 Error Tables
 Safety I/O Units
Event code
Event name
05200000 hex
System Error
05210000 hex
Internal Cir-
cuit Error at
Safety Input
05220000 hex
Internal Cir-
cuit Error at
Test Output
05230000 hex
Internal Cir-
cuit Error at
Safety Out-
put
35210000 hex
Safety Pro-
cess Data
Communica-
tions Not
Established -
Incorrect Unit
Parameter
Error
35230000 hex
Safety Pro-
cess Data
Communica-
tions Not
Established,
Incorrect
FSoE Slave
Address
Error
35240000 hex
Safety Pro-
cess Data
Communica-
tions Not
Established,
Incorrect
Frame Error
65200000 hex
I/O Power
Supply Volt-
age Error
65210000 hex
Output
Power Inter-
rupt Circuit
Error
65220000 hex
External Test
Signal Fail-
ure at Safety
Input
3-180
Meaning
Assumed cause
A hardware error
• Hardware has failed.
was detected
• A memory error occurred due to
during self-diagno-
a transient cause, such as a
sis of the hardware.
software error or excessive
noise.
A fault was
• The internal circuit for the
detected in the
safety input terminal is faulty.
internal circuit for
• A memory error or signal error
the safety input ter-
occurred due to a transient
minal.
cause, such as a software error
or excessive noise.
A fault was
• The internal circuit for the test
detected in the
output terminal is faulty.
internal circuit for
• A memory error or signal error
the test output ter-
occurred due to a transient
minal.
cause, such as a software error
or excessive noise.
A fault was
• The internal circuit for the
detected in the
safety output terminal is faulty.
internal circuit for
• A memory error or signal error
the safety output
occurred due to a transient
terminal.
cause, such as a software error
or excessive noise.
Safety process data
• The model or safety I/O termi-
communications
nal settings are not correct.
was not estab-
lished with the
Safety CPU Unit.
Safety process data
• The setting of the FSoE slave
communications
address in the safety process
was not estab-
data communications settings
lished with the
is different from the setting in
Safety CPU Unit
the Unit.
because of an
incorrect FSoE
slave address.
Safety process data
• An incorrect frame was
communications
received in safety process data
was not estab-
communications. There is
lished with the
excessive noise.
Safety CPU Unit
because an incor-
rect frame was
received.
An incorrect I/O
• The input power or output
power supply volt-
power is not supplied correctly.
age was detected.
An error was
• The wiring is not correct or
detected by the out-
there is a fault in the hardware.
put power interrup-
tion test.
An error was
• The positive power supply wire
detected in test
is in contact with the input sig-
pulse evaluation of
nal line.
the safety input ter-
• The input signal lines are
minals.
shorted.
• The external device is faulty.
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
S
S
S
S
NJ/NX-series Troubleshooting Manual (W503)
Reference
Z930
Z930
Z930
Z930
Z930
Z930
Z930
Z930
Z930
Z930