Omron NX701-17 Series Troubleshooting Manual page 84

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

3 Error Tables
Event code
Event name
10060000 hex
SD Memory
Card Data
Corrupted
10070000 hex
SD Memory
Card Access
Power OFF
Error
10130000 hex
PLC System
(Ver. 1.13 or
Information
later)
10310000 hex
Incorrect SD
(Ver. 1.02 or
Memory Card
later)
Removal
3-6
Meaning
Assumed cause
A file that must be
• The Controller power supply
in the SD Memory
was turned OFF while the SD
Card is missing or
BUSY indicator was lit.
corrupted.
• The power supply to the Con-
troller was interrupted momen-
tarily while the SD BUSY
indicator was lit.
• The SD Memory Card was
removed while the SD PWR
indicator was lit.
• The SD Memory Card is dam-
aged.
The power supply
• The Controller power supply
to the Controller
was turned OFF while the SD
was interrupted
BUSY indicator was lit.
during access to
• The power supply to the Con-
the SD Memory
troller was interrupted momen-
Card.
tarily while the SD BUSY
indicator was lit.
This event pro-
• This event provides internal
vides internal infor-
information from the PLC Func-
mation from the
tion Module. It is recorded to
PLC Function Mod-
provide additional information
ule.
for another event.
SD Memory Card
• The SD Memory Card was
removal process-
removed while the SD PWR
ing failed.
indicator was lit.
Level
Maj
Prt
Min
Obs Info
U
S
S
S
S
NJ/NX-series Troubleshooting Manual (W503)
Reference
W500, W535,
W578
W500, W535,
W578
W578
W500, W535,
W578

Advertisement