3 Error Tables
Event code
Event name
35910000 hex
Unregistered
(Ver. 1.13 or
NX Unit
later)
Mounted
35930000 hex
NX Unit
(Ver. 1.13 or
Serial Num-
later)
ber Mismatch
44440000 hex
NX Bus
(Ver. 1.13 or
Function Pro-
later)
cessing Error
85540000 hex
NX Bus I/O
(Ver. 1.13 or
Communica-
later)
tions Stopped
Due to
Another
Event
35920000 hex
Registered
(Ver. 1.13 or
NX Unit Not
later)
Mounted
85500000 hex
NX Bus Com-
(Ver. 1.13 or
munications
later)
Error
3-62
Meaning
Assumed cause
There is a mounted
• There is a mounted Unit that
NX Unit that does
does not exist in the Unit con-
not exist in the Unit
figuration information registered
configuration infor-
in the CPU Unit.
mation registered in
• There is a mounted Unit in
the CPU Unit.
which the NX Unit Mounting
Setting is set to Disabled.
If there are more
than one NX Unit
relevant to this
event, only the NX
Unit that is nearest
to the CPU Unit is
registered with the
event.
There is a mounted
• There is no mounted NX Unit
NX Unit with a
with the serial number that you
serial number differ-
set in the Unit configuration
ent from that in the
information registered in the
Unit configuration
CPU Unit.
information regis-
tered in the CPU
Unit.
A fatal error was
• An error occurred in the soft-
detected in the NX
ware.
Bus Function Mod-
ule.
The I/O communi-
• I/O refreshing was stopped
cations on the NX
based on the Fail-soft Opera-
bus were stopped
tion Setting.
based on the Fail-
soft Operation Set-
ting because an
error that triggers
fail-soft operation
occurred.
There is no
• There is no mounted NX Unit
mounted NX Unit
that exists in the Unit configura-
that exists in the
tion information registered in
Unit configuration
the CPU Unit.
information regis-
• The power supply to the Addi-
tered in the CPU
tional NX Unit Power Supply
Unit.
Unit is not turned ON.
If there are more
than one NX Unit
relevant to this
event, only the NX
Unit that is nearest
to the CPU Unit is
registered with the
event.
A communications
• The NX bus connector contact
error that prevents
is faulty due to vibration or
normal NX bus
shock.
communications
• Excessive noise is applied to
was detected.
the NX bus connector.
If there are more
• An NX Unit was removed.
than one NX Unit
• An error occurred in an NX
relevant to this
Unit.
event, only the NX
Unit that is nearest
to the CPU Unit is
registered with the
event.
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
NJ/NX-series Troubleshooting Manual (W503)
Reference
W501, W578
W501, W578
W501, W578
W501, W578
W501, W578
W501, W578

Advertisement