Omron NX701-17 Series Troubleshooting Manual page 187

Machine automation controller nj/nx-series
Hide thumbs Also See for NX701-17 Series:
Table of Contents

Advertisement

Event code
Event name
35300000 hex
DB Connec-
tion Setting
Error
85100000 hex
DB Connec-
tion Discon-
nected Error
95300000 hex
DB Connec-
tion Service
Started
95310000 hex
DB Connec-
tion Service
Stopped
95320000 hex
DB Connec-
tion Service
Shutdown
NJ/NX-series Troubleshooting Manual (W503)
Meaning
Assumed cause
The DB Connec-
• The power supply to the Con-
tion settings are not
troller was interrupted during a
correct.
download of the DB Connection
settings.
• The DB Connection settings
are not correct because the
power supply to the Controller
was interrupted during a Clear
All Memory operation.
• The DB Connection settings
are not correct because the
power supply to the Controller
was interrupted during a
Restore operation.
• Non-volatile memory failed.
The DB Connec-
• The power supply to the server
tion was discon-
is OFF.
nected due to an
• The DB is stopped in the
error.
server.
• The Ethernet cable connector is
disconnected.
• The Ethernet cable is broken.
• Noise
The DB Connec-
• The DB Connection Service
tion Service was
was successfully started.
started.
The DB Connec-
• The DB Connection Service
tion Service was
was stopped.
stopped.
The DB Connec-
• The DB Connection Service
tion Service was
was shut down for turning OFF
shut down.
the power supply safely.