Omron FQ2-S4 User Manual page 371

Smart camera
Hide thumbs Also See for FQ2-S4:
Table of Contents

Advertisement

Note
During execution of continuous measurements, the BUSY signal remains ON. The Vision Sensor will acknowledge
the EXE signal only after the End Continuous Measurements command is executed.
● Data Output after Measurements When Handshaking Is Enabled
Data Output
Request Bit (DSA)
Command
signal
Area
Data Output
Response
Completed (GATE)
Area
signal
Output data 1
Output Area
to 64(DATA1 to
DATA64)
Here, the Vision Sensor ends
measurements and can output data.
(1)
After measurements are completed, the Data Output Request Bit (DSA) signal is turned ON by the PLC and a request is
made to the Vision Sensor to output the data.
(2)
The Vision Sensor outputs the data. After the data is output, the Data Output Completed (GATE) signal turns ON.
(3)
The master confirms that the Data Output Completed (GATE) signal has turned ON, loads the data, and turns OFF the
Data Output Request Bit (DSA) signal.
(4)
When the Vision Sensor detects that the Data Output Request (DSA) signal is OFF, it automatically turns OFF the Data
Output Completed (GATE) signal.
(5)
The Data Output Request Bit (DSA) signal is turned ON from the PLC and a request is made to output the data.
*1 I
f the data output request signal is not manipulated within the control timeout time (100 to 120,000 ms) in the
EtherNet/IP settings, and data output error will occur and the ERR signal will turn ON. When the ERCLR signal is turned
ON, the ERR signal will turn OFF. However, if a timeout occurs again, the ERR signal will turn ON again. Therefore,
correctly request data output (DSA control) or execute a Clear Data Output Buffer command.
*2 Indicates that the data to output is separated and output more than once.
● Data Output after Measurements When Handshaking Is Disabled
Data Output
Response
Completed
Area
(GATE) signal
Output data 1 to 64
(DATA1 to DATA64)
Output Area
Here, the Vision Sensor ends measurements and can output data.
FQ2-S4 User's Manual
First data output
*1
ON
OFF
ON
OFF
ON
OFF
(1)
(2)
(3)
(4)
(1)
(2)
ON
OFF
ON
OFF
Outputting Data and Controlling Operation through EtherNet/IP
*2
Second data output
*1
(5)
The data is output according to the set
output cycle (1) and output time (2).
After data output is completed, the
GATE signal turns ON and the output
data is maintained for the data output
hold time.
369

Advertisement

Table of Contents
loading

Table of Contents