Clear Measurement Values
This command clears the measurement values that are stored in the Sensor. However, the OR signal and the
output signals that are assigned to OUT0 to OUT2 are not cleared.
Note
This function can be used in Run Mode only.
Settings
[In/Out] − [I/O setting] − [I/O setting] − [Input] − [Input mode]
Press [Expand mode].
Wiring
Color
Signal
Gray
IN0
Green
IN1
Red
IN2
White
IN3
Purple
IN4
Yellow
IN5
Orange
OUT1 (BUSY)
Timing Chart
IN0 to IN4 signals
ON
IN5 signal
OFF
ON
BUSY signal
OFF
298
Controlling Operation and Outputting Data with the Sensor's Standard Parallel Connection
State
Description
ON
Command parameter for clearing mea-
surement values
OFF
ON
OFF
OFF
ON
Command input for clearing measure-
ment values
--
Processing in progress (default)
Allow 5 ms min. and then
turn ON IN5.
ON for 1 ms min.
The measurement values are
cleared from the Sensor.
The signals shown at the left
are used.
Refer to the following
information for signal wiring.
2-4 Wiring: p. 42
1 Turn ON IN0 and IN2 and turn OFF
IN3 and IN4.
2 Turn ON the IN5 signal while the
BUSY signal is OFF to clear the
measurement values.