5 Calibration
5.3 Updating revolution counters
Continued
Make sure the axes are positioned according to the correct calibration values, not
only according to the synchronization marks. The correct values are found on a
label, located either on the lower arm, underneath the flange plate on the base or
on the frame.
At delivery the manipulator is in the correct position. Do NOT rotate axis 4 or 6 at
power up before the revolution counters are updated.
If one of the following mentioned axes are rotated one or more turns from its
calibration position before updating the revolution counter, the correct calibration
position will be lost due to non-integer gear ratio. This affects the following
manipulators:
Manipulator variant
IRB 6620
If the synchronization marks seem to be wrong (even if the motor calibration data
is correct), try to rotate the axis one turn, update the revolution counter and check
the synchronization marks again (try both directions, if needed).
Step 2 - Updating the revolution counter with the FlexPendant
Use this procedure to update the revolution counter with the FlexPendant (IRC5).
1
Continues on next page
308
Action
On the ABB menu, tap Calibration.
xx1500000942
© Copyright 2006-2020 ABB. All rights reserved.
Axis 4
Yes
Axis 6
No
Product manual - IRB 6620
3HAC027151-001 Revision: W