Delta C200 Series User Manual page 86

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Chapter 10 Summary of Parameter Settings|C200 Series
06 Protection Parameters
Parameter
06-00
Low Voltage Level
Over-voltage Stall
06-01
Prevention
Selection for Over-voltage
06-02
Stall Prevention
Over-current Stall
06-03
Prevention during
Acceleration
Over-current Stall
Prevention during
06-04
Operation
Accel. /Decel. Time
Selection of Stall
06-05
Prevention at Constant
Speed
Over-torque Detection
06-06
Selection (OT1)
Over-torque Detection
06-07
Level (OT1)
Over-torque Detection
06-08
Time (OT1)
Over-torque Detection
06-09
Selection (OT2)
Over-torque Detection
06-10
Level (OT2)
Over-torque Detection
06-11
Time (OT2)
06-12
Current Limit
Electronic Thermal Relay
06-13
Selection (Motor 1)
Electronic Thermal
06-14
Characteristic for Motor 1
Heat Sink Over-heat (OH)
06-15
Warning
Stall Prevention Limit
06-16
Level
06-17
Present Fault Record
Second Most Recent Fault
06-18
Record
Call 1(800)985-6929 for Sales
deltaacdrives.com
Explanation
230V: 150.0~220.0Vdc
460V: 300.0~440.0Vdc
0: Disabled
230V: 0.0~450.0Vdc
460V: 0.0~900.0Vdc
0: Traditional over-voltage stall prevention
1: Smart over-voltage prevention
Normal Load: 0~160%(100%: drive's rated current)
Heavy Load: 0~180%(100%: drive's rated current)
Normal Load: 0~160%(100%: drive's rated current)
Heavy Load: 0~180%(100%: drive's rated current)
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel
0: No function
1: Over-torque detection during constant speed
operation, continue to operate after detection
2: Over-torque detection during constant speed
operation, stop operation after detection
3: Over-torque detection during operation, continue to
operate after detection
4: Over-torque detection during operation, stop
operation after detection
10~250% (100%: drive's rated current)
0.0~60.0 sec.
0: No function
1: Over-torque detection during constant speed
operation, continue to operate after detection
2: Over-torque detection during constant speed
operation, stop operation after detection
3: Over-torque detection during operation, continue to
operation after detection
4: Over-torque detection during operation, stop
operation after detection
10~250% (100%: drive's rated current)
0.1~60.0 sec.
0~250% (100%: drive's rated current)
0: Inverter motor
1: Standard motor
2: Disable
30.0~600.0 sec.
0.0~110.0℃
0~100% (Pr.06-03, Pr.06-04)
0: No fault record
1: Over-current during acceleration (ocA)
deltaacdrives.com
Settings
10-18
sales@deltaacdrives.com
Factory
Setting
180.0
360.0
380.0
760.0
0
120
150
120
150
0
0
120
0.1
0
120
0.1
150
2
60.0
85.0
50
0
0
sales@deltaacdrives.com

Advertisement

Table of Contents
loading

Table of Contents