14.6.4 Explanation for the Application Commands
API
CALL
01
Bit Devices
X
Y
Operands:
S: Operand S can designate P.
Operand S of C2000 series can designate P0~P63.
Explanation
Call 1(800)985-6929 for Sales
S
P
Word Devices
M
K
H KnX KnY KnM T
1. S: The pointer of call subroutine.
2. Edit the subroutine designated by the pointer after FEND instruction.
3. If only CALL instruction is in use, it can call subroutines of the same pointer
number with no limit of times.
4. Subroutine can be nested for 5 levels including the initial CALL instruction. (If
entering the sixth level, the subroutine won't be executed.)
deltaacdrives.com
Call Subroutine
16-bit command (3 STEPS)
CALL
C
D
32-bit command
Flag signal: None
14-41
deltaacdrives.com
sales@deltaacdrives.com
Chapter 14 PLC Function |C200 Series
CALLP
sales@deltaacdrives.com