Delta C200 Series User Manual page 140

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Settings 0.000~65000 ms
It is used to improve the unstable speed or unstable position due to the insufficient of analog
resolution. It needs to be used with external terminal (set to 43). After setting this parameter, it
needs to adjust the analog output resolution of controller simultaneously by this setting.
AUI +10V
AUI 0V
AUI - 10V
F requenc y
command
Output
frequency
0Hz
Resolution
switch
MI=43
Display the Status of Multi-function Input Terminal
For Example:
If Pr.02-50 displays 0034h (Hex), i.e. the value is 52, and 110100 (binary). It means MI1, MI3 and
MI4 are active.
Weights
Bit
Status of Multi-function Output Terminal
For Example:
If Pr.02-51 displays 000Bh (Hex), i.e. the value is 11, and 1011 (binary). It means RY1, RY2 and
MO1 are ON.
Call 1(800)985-6929 for Sales
deltaacdrives.com
Acc el./D ecel. time
01-12~01-19
Max. output frequency
01-00
Delay time for max .
frequency switch
10-24
F or war d r unni ng
Weights
9
2
2
Bit
9
8
0=On
1=Off
2
5
2
4
2
3
2
2
2
1
2
0
1
1
0
1
0
0
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
Resolution switch
R esolution sw itch
frequency
frequency
10-25
10-25
ON
8
7
6
5
4
3
2
1
0
2
2
2
2
2
2
2
2
7
6
5
4
3
2
1
0
0=O N
1=O FF
MI1
Settings
MI2
5
4
= bit5x 2 +bit4x2 +bit2x2
MI3
5
4
= 1x2 +1x2 + 1x2
MI4
=32+16+4 =52
MI5
MI6
11-41
sales@deltaacdrives.com
Max. output frequency
01-00
Delay time for max .
frequency switch
10-24
Revers e running
Factory Setting: Read only
F W D
RE V
MI1
MI2
MI3
MI4
MI5
MI6
MI7
MI8
2
2
NOTE
5
4
3
2 =322 =1 6
2 =8
1
0
2 =2
2 =1
Factory Setting: Read only
sales@deltaacdrives.com
2
2 =4