Delta C200 Series User Manual page 102

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
NOTE
1. It can display negative values when setting analog input bias (Pr.03-03~03-10).
Example: assume that AVI input voltage is 0V, Pr.03-03 is 10.0% and Pr.03-07 is 4 (Serve bias as the
center).
2. Example: If REV, MI1 and MI6 are ON, the following table shows the status of the terminals.
0: OFF, 1: ON
If REV, MI1 and MI6 are ON, the value is 0000 0000 1000 0110 in binary and 0086h in HEX. When
Pr.00-04 is set to "16" or "19", it will display "0086h" with LED U is ON on the keypad KPC-CE01. The
setting 16 is the status of digital input by Pr.02-12 setting and the setting 19 is the corresponding CPU
pin status of digital input, the FWD/REV action and the three-wire MI are not controlled by Pr.02-12.
User can set to 16 to monitor digital input status and then set to 19 to check if the wire is normal.
3. Assume that RY1: Pr.02-13 is set to 9 (Drive ready). After applying the power to the AC motor drive, if
there is no other abnormal status, the contact will be ON. The display status will be shown as follows.
N.O. switch status:
Terminal
Reserved
Status
0
At the meanwhile, if Pr.00-04 is set to 17 or 20, it will display in hexadecimal "0001h" with LED U is ON
on the keypad. The setting 17 is the status of digital output by Pr.02-18 setting and the setting 20 is the
corresponding CPU pin status of digital output. User can set 17 to monitor the digital output status and
then set to 20 to check if the wire is normal.
4. Setting 8: 100% means the motor rated torque. Motor rated torque = (motor rated power x60/2π)/motor
rated speed
5. If Pr.00-04 = 25, when display value reaches 100.00%, the drive will show "oL" as an overload warning.
Coefficient Gain in Actual Output Frequency
Settings 0~160.00
This parameter is to set coefficient gain in actual output frequency. Set Pr.00-04= 31 to display the
calculation result on the screen (calculation = output frequency * Pr.00-05).
Call 1(800)985-6929 for Sales
20: The corresponding CPU pin status of digital output (0.) (refer to NOTE
3)
21~24: Reserved
25: Overload counting (0.00~100.00%) (o.) (Refer to Note 5)
26: GFF Ground Fault (Unit :%)(G.)
27: DC Bus voltage ripple (Unit: Vdc)(r.)
28: Display PLC register D1043 data (C) display in hexadecimal
29: Reserved
30 : Display output of user defined (U)
31 : H page x 00-05 Display user Gain(K)
32~34: Reserved
35: Control Mode display: 0= Speed control mode (SPD), 1= torque control
mode (TQR) (t.)
36: Present operating carrier frequency of drive (Hz) (J.)
Terminal MI8 MI7 MI6 MI5 MI4 MI3 MI2 MI1 REV FWD
Status
0
0
Reserved
0
0
0
0
0
0
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
1
0
0
0
0
Reserved
0
0
0
0
0
11-3
deltaacdrives.com
sales@deltaacdrives.com
1
1
0
DFM2
DFM1 Reserved RY2 RY1
0
0
0
Factory Setting: 0
sales@deltaacdrives.com
0
1