Delta C200 Series User Manual page 250

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Display on
KPE-LE02
Warning
CAN/M G uard err
Warning
CAN/M bus off
Warning
CAN/M Node Lack
Warning
Warning
CAN/M SDO over
Warning
CAN/M Sdo Tout
Warning
CAN/M Addres set
Fault
Oc at accel
Fault
Oc at decel
Fault
Oc at normal SPD
Call 1(800)985-6929 for Sales
deltaacdrives.com
Display on
KPC-CC01
CAN Master guarding error
PCGd
CAN Master bus off
PCbF
CAN Master node error
PCnL
CAN/M cycle time-out
PCCt
CAN/M SDOover
PCSF
CAN/M SDO time-out
PCSd
CAN/M station address error
PCAd
Over-current during acceleration
(Output current exceeds triple rated current during acceleration.)
ocA
Corrective Actions:
1. Short-circuit at motor output: Check for possible poor insulation at the
output lines.
2. Acceleration Time too short: Increase the Acceleration Time.
3. AC motor drive output power is too small: Replace the AC motor
drive with the next higher power model.
Over-current during deceleration
(Output current exceeds triple rated current during deceleration.)
ocd
Corrective Actions:
1. Short-circuit at motor output: Check for possible poor insulation at the
output line.
2. Deceleration Time too short: Increase the Deceleration Time.
AC motor drive output power is too small: Replace the AC motor drive with
the next higher power model.
Over-current during steady state operation
(Output current exceeds triple rated current during constant speed.)
ocn
Corrective Actions:
1. Short-circuit at motor output: Check for possible poor insulation at the
output line.
2. Sudden increase in motor loading: Check for possible motor stall.
AC motor drive output power is too small: Replace the AC motor drive with
the next higher power model.