Set Pr.05-00=4 and press [Run] to begin auto-tuning. Please be aware of the motor that it
starts spinning as [Run] is pressed.
4.
When auto-tuning is completed, please check if the PG offset angle is written into Pr.05-42
automatically.
NOTE
When auto-tuning for PM motor is completed and the control mode setting is done, it is
recommend to turn the drive's power off and restart again to ensure the drive operates according
to the motor parameter settings.
Full-load Current of Induction Motor 1(A)
Settings 10 to 120% of drive's rated current
This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. The factory setting is 90% X rated current.
Example: The rated current for 7.5HP (5.5kW) is 25 and factory setting is 22.5A. The range for
setting will be 10~30A.(25*40%=10A and 25*120%=30A)
Rated Power of Induction Motor 1(kW)
Settings 0~655.35 kW
It is used to set rated power of the motor 1. The factory setting is the power of the drive.
Rated Speed of Induction Motor 1 (rpm)
Settings 0~65535
It is used to set the rated speed of the motor and need to set according to the value indicated on
the motor nameplate.
Pole Number of Induction Motor 1
Settings 2~20
It is used to set the number of motor poles (must be an even number).
No-load Current of Induction Motor 1 (A)
Settings 0 to the factory setting in Pr.05-01
The factory setting is 40% X rated current.
Stator Resistance(Rs) of Induction Motor 1
Rotor Resistance(Rr) of Induction Motor 1
Call 1(800)985-6929 for Sales
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
11-74
deltaacdrives.com
sales@deltaacdrives.com
Unit: Ampere
Factory Setting: #.##
Factory Setting: #.##
Factory Setting:
1710(60Hz 4 poles)
1410(50Hz 4 poles)
Factory Setting: 4
Unit: Amper
Factory Setting: #.##