14.5.4 Communication Address for PLC Devices
Device
X
Y
T
M
M
C
D
D
Function Code
Function Code
Only when PLC is at Stop status, PLC data can be read/write via communication device. When PLC
is at Run status, the communication address should be the mapping address, e.g. for Pr.04-00 it
maps to 0400H.
NOTE
When PLC function is activated, C2000 can Read/Write the PLC and drive's parameter by different addresses (pre-defined
station number for the AC motor drive is 1, for PLC station number is 2)
Call 1(800)985-6929 for Sales
Range
00~17 (Octal)
00~17 (Octal)
00~159
000~799
1000~1079
0~79
00~399
1000~1099
01
02
03
Force changing one coil status
05
06
Force changing multiple coil
0F
10
deltaacdrives.com
Type
bit
bit
bit/word
bit
bit
bit/word
word
word
Description
Read coil status
Read input status
Read one data
Write in one data
status
Write in multiple data
14-26
deltaacdrives.com
sales@deltaacdrives.com
Chapter 14 PLC Function |C200 Series
Address (Hex)
0400~040F
0500~050F
0600~069F
0800~0B1F
0BE8~0C37
0E00~0E47
1000~118F
13E8~144B
Supported Devices
Y, M, T, C
X,Y,M,T,C
T,C,D
Y,M,T,C
T,C,D
Y,M,T,C
T,C,D