Delta C200 Series User Manual page 316

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Ladder diagram:
Example
Mnemonic
Store the current result of the internal PLC operations
MPS
Operand
To save contents of the accumulative register into the operation result. (the result
operation pointer pluses 1)
Mnemonic
Reads the current result of the internal PLC operations
MRD
Operand
Reading content of the operation result to the accumulative register. (the pointer of
operation result doesn't move)
Mnemonic
Reads the current result of the internal PLC operations
MPP
Operand
Reading content of the operation result to the accumulative register. (the stack pointer
will decrease 1)
Ladder diagram:
Example
Call 1(800)985-6929 for Sales
deltaacdrives.com
Block A
X0
X1
X2
X3
Block B
MPS
X0
X1
X2
MRD
MPP
deltaacdrives.com
Chapter 14 PLC Function |C200 Series
Command code: Operation:
LD
Y1
ANI
LDI
ORB
AND
ORB
OUT
Function
None
Function
None
Function
None
Command code: Operation:
LD
MPS
Y1
AND
M0
OUT
Y2
MRD
END
AND
OUT
MPP
OUT
END
14-31
sales@deltaacdrives.com
X0
Load contact A of X0
Connect to contact B of
X1
X1 in series
Load contact B of X2
X2
Connect to contact A of
X3
X3 in series
Connect circuit block in
parallel
Y1
Drive Y1 coil
X0
Load contact A of X0
Save in stack
Connect to contact A of
X1
X1 in series
Y1
Drive Y1 coil
Read from the stack
(without moving
pointer)
Connect to contact A of
X2
X2 in series
Drive M0 coil
M0
Read from the stack
Drive Y2 coil
Y2
End program
sales@deltaacdrives.com

Advertisement

Table of Contents
loading

Table of Contents