Delta C200 Series User Manual page 120

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
JOG Frequency
Settings 0.00~600.00Hz
Both external terminal JOG and key "F1" on the keypad KPC-CC01 can be used. When the jog
command is ON, the AC motor drive will accelerate from 0Hz to jog frequency (Pr.01-22). When the
jog command is OFF, the AC motor drive will decelerate from Jog Frequency to zero. The Jog
Accel./Decel. time (Pr.01-20, Pr.01-21) is the time that accelerates from 0.0Hz to Pr.01-22 JOG
Frequency.
The JOG command can't be executed when the AC motor drive is running. In the same way, when
the JOG command is executing, other operation commands are invalid except forward/reverse
commands and STOP key on the digital keypad.
It does not support JOG function in the optional keypad KPC-CE01.
1st/4th Accel./decel. Frequency
Settings 0.00~600.00Hz
The transition from acceleration/deceleration time 1 to acceleration/deceleration time 4, may also
be enabled by the external terminals. The external terminal has priority over Pr. 01-23.
S-curve Acceleration Begin Time 1
S-curve Acceleration Arrival Time 2
S-curve Deceleration Begin Time 1
Call 1(800)985-6929 for Sales
Frequency
01-00
M ax. O utput
Frequency
Frequency
Setting
accel. time
01-12,14,16,18,20
F reque nc y
1st Acceler ati on
Time
01-23
4th A cceleratio n
Time
1st/4th A cceleratio n/Dec eleration F requenc y S witch i ng
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
decel. time
01-13,15,17,19,21
Accel./Decel. Time
4th Dec ele ration
1s t Dec eleratio n
11-21
deltaacdrives.com
sales@deltaacdrives.com
Time
Factory Setting: 6.00
Factory Setting: 0.00
T ime
T ime
Ti me
sales@deltaacdrives.com

Advertisement

Table of Contents
loading

Table of Contents