Chapter 11 Description of Parameter Settings|C200 Series
Set frequency com man d
(Hig her th an switch ing comm and)
Perfo rm RUN co mm and
Can the d rive run
NO
no rm ally until switching
to higher freque ncy?
Whe n running at high
NO
frequency, is the freq uency
stable?
Increase load an d Test
Proced ure for switching between I
F mo de and FOC mo de
11-138
deltaacdrives.com
sales@deltaacdrives.com
Observe output current
fequen cy via
Yes
co mm nucation intreface
Obse rve o utput current
fequency via
Yes
com mnucation in treface
/