230V
Pr.06-55=1
Pr.06-55=0 or 2
(50℃: UL open-type)
(40℃:UL type1 or open type_size by size)
110
100
90
80
70
60
50
40
2
3
Model No.
VFD004CB21A-20/-21/-21M
VFD007CB21A-20/-21/-21M
VFD015CB21A-20/-21/-21M
VFD022CB21A-20/-21/-21M
VFD004CB23A-20/-21/-21M
VFD007CB23A-20/-21/-21M
VFD015CB23A-20/-21/-21M
VFD022CB23A-20/-21/-21M
VFD037CB23A-20/-21/-21M
VFD007CB43A-20/-21/-21M
VFD015CB43A-20/-21/-21M
VFD022CB43A-20/-21/-21M
VFD037CB43A-20/-21/-21M
VFD040CB43A-20/-21/-21M
VFD055CB43A-20/-21/-21M
VFD075CB43A-20/-21/-21M
The required airflow shown in chart is for installing one
※
Call 1(800)985-6929 for Sales
VFD004~037CB23A
VFD004~022CB21A
4
5
6
7
8
9 10 11 12 13 14 15
The mounting clearances stated in the figure is for installing the drive in
※
an open area. To install the drive in a confined space (such as cabinet
or electric box), please follow the following three rules: (1) Keep the
minimum mounting clearances. (2) Install a ventilation equipment or an
air conditioner to keep surrounding temperature lower than operation
temperature. (3) Refer to parameter setting and set up Pr. 00-16,
Pr.00-17, and Pr. 06-55.
The following table shows heat dissipation and the required air volume
※
when installing a single drive in a confined space. When installing
multiple drives, the required air volume shall be multiplied by the
number the drives.
Refer to the chart (Air flow rate for cooling) for ventilation equipment
※
design and selection.
Refer to the chart (Power dissipation) for air conditioner design and
※
selection.
Minimum mounting clearances:
Frame
A~C
Air flow rate for cooling
Flow Rate
(cfm)
-
-
15
15
-
-
15
15
15
-
-
15
15
15
15
24
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
230V
Pr.06-55=0 or 2
(40℃: UL open-type)
(30℃: UL type1 or open type_size by size)
110
100
90
80
70
60
50
Fc
(kHz)
40
2
NOTE
A (mm)
B (mm)
60
30
Loss External
Flow Rate
3
(m
/hr)
(Heat sink)
16
-
32
-
26
60
26
85
21
-
35
-
26
56
26
82
26
118
-
35
-
47
26
75
26
110
26
126
26
145
41
212
The heat dissipation shown in the chart is for
※
11-96
deltaacdrives.com
sales@deltaacdrives.com
VFD004~037CB23A
VFD004~022CB21A
3
4
5
6
7
8
9 10 11 12 13 14 15
C (mm)
10
Power Dissipation
Internal
20
39
52
69
17
26
32
34
43
24
27
30
33
34
37
83
sales@deltaacdrives.com
Fc
(kHz)
D (mm)
0
Total
36
72
112
154
37
61
89
116
161
59
74
105
143
160
181
295