Delta C200 Series User Manual page 215

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Settings 0: Warn and keep operation
This parameter is valid only when the feedback signal is ACI.
AC motor drive acts when the feedback signals (analog PID feedback or PG (encoder) feedback)
are abnormal.
Sleep Frequency
Settings Pr.08-18=0: 0.00~600.00Hz
Wake-up Frequency
Settings Pr.08-18=0: 0.00~600.00Hz
Sleep Time
Settings 0.00~6000.0 sec
If the command frequency falls below the sleep frequency, for the specified time in Pr. 08-12, then
the drive will shut off the output and wait until the command frequency rises above Pr.08-11.
Wake-up frequency
PID Deviation Level
Settings 1.0~50.0%
PID Deviation Time
Settings 0.1~300.0 sec
Filter Time for PID Feedback
Settings 0.1~300.0 sec
When the PID control function is normal, it should calculate within a period of time and close to the
setpoint value.
Refer to the PID control diagram for details. When executing PID feedback control, if |PID
reference target value – detection value| > Pr.08-13 PID Deviation Level and exceeds Pr.08-14
Call 1(800)985-6929 for Sales
deltaacdrives.com
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
Pr.08-18=1: 0.00~200.00%
Pr.08-18=1: 0.00~200.00%
Frequency command
08-11
08-10
Sleep frequency
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
actual output frequency
sleep time
08-12
Sleep Function
11-116
sales@deltaacdrives.com
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 0.0
0Hz
Factory Setting: 10.0
Factory Setting: 5.0
Factory Setting: 5.0
sales@deltaacdrives.com