It will be recorded as the following table:
First fault
Second fault
Third fault
Seven fault
Time interval between errors occur (day)
Settings Read only
Time interval between errors occur (minute)
Settings Read only
Low Current Setting Level
Settings 0.0 ~ 6553.5 %
Low Current Detection Time
Settings 0.00 ~ 655.35 sec
Treatment for low current
Call 1(800)985-6929 for Sales
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
Pr.06-17
ovA
Pr.06-17
ovd
Pr.06-18
ovA
Pr.06-17
ovA
Pr.06-18
ovd
Pr.06-19
ovA
Pr.06-17
ocS
Pr.06-18
ocA
Pr.06-19
ocA
Pr.06-20
ovA
Pr.06-21
ovd
Pr.06-22
ovA
11-98
deltaacdrives.com
Pr.06-63
3000 ovA occurs at the 3000 min
after operating.
Pr.06-63
3482
ovd occurs at 482 min after
last fault (ovA)
Pr.06-64
3000
Pr.06-63
4051
ovA occurs at 569 min after
last fault (ovd)
Pr.06-64
3482
Pr.06-65
3000
Pr.06-63
12
(12-5824)+64800=58988 min
ocS occurs at 58988 min after
last fault (ocA)
Pr.06-64
5824
Pr.06-65
5003
Pr.06-66
4051
Pr.06-67
3482
Pr.06-68
3000
Factory Setting: Read only
Factory Setting: Read only
Factory Setting: 0.0
Factory Setting: 0.00
Factory Setting: 0
sales@deltaacdrives.com
3482-3000=482 min
4051-3482=569 min