Delta C200 Series User Manual page 125

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
02 Digital Input/Output Parameter
2-wire/3-wire Operation Control
Settings 0: 2 wire mode 1
It is used to set the operation control method:
2-wire mode 1
FWD/STOP
REV/STOP
2-wire mode 2
RUN/STOP
3-wire operation control
Multi-function Input Command 1 (MI1) (MI1= STOP command when in 3-wire operation
control)
Multi-function Input Command 2 (MI2)
Multi-function Input Command 3 (MI3)
Multi-function Input Command 4 (MI4)
Multi-function Input Command 5 (MI5)
Multi-function Input Command 6 (MI6)
Multi-function Input Command 7 (MI7)
Multi-function Input Command 8 (MI8)
Settings
0: no function
1: multi-step speed command 1/multi-step position command 1
2: multi-step speed command 2/multi-step position command 2
3: multi-step speed command 3/multi-step position command 3
Call 1(800)985-6929 for Sales
1: 2 wire mode 2
2: 3 wire mode
Pr.02-00
0
1
REV/FWD
3
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
This parameter can be set during operation.
Control Circuits of the External Terminal
FWD/STOP
REV/STOP
RUN/STOP
FWD/REV
RUN
STOP
REV/FWD
11-26
deltaacdrives.com
sales@deltaacdrives.com
Factory Setting: 0
FWD:("OPEN":STOP)
("CLOSE":FWD)
REV:("OPEN": STOP)
("CLOSE": REV)
DCM
VFD-Cx
FWD:("OPEN":STOP)
("CLOSE":RUN)
REV:("OPEN": FWD)
("CLOSE": REV)
DCM
VFD-Cx
FWD "CLOSE":RUN
MI1 "OPEN":STOP
REV/FWD "OPEN": FWD
"CLOSE": REV
DCM
VFD-Cx
Factory Setting: 1
Factory Setting: 2
Factory Setting: 3
Factory Setting: 4
Factory Setting: 0