When external terminal MI is set to 41 and 42 (AUTO/HAND mode), the settings Pr.00-29=1, 2, 3,
4 will be disabled. The external terminal has the highest priority among all command, Pr.00-29 will
always function as Pr.00-29=0, standard HOA mode.
When Pr.00-29 is not set to 0, Local/Remote function is enabled, the top right corner of digital
keypad (KPC-CC01) will display "LOC" or "REM" (the display is available when KPC-CC01 is
installed with firmware version higher than version 1.021). The LOCAL frequency and source of
operation can be set by Pr.00-20 and Pr.00-21, and the REMOTE frequency and source of
operation can be set by Pr.00-30 and Pr.00-31. Local/Remote function can be selected or switched
by using digital keypad(KPC-CC01) or setting external terminal MI=56. The AUTO key of the digital
keypad now controls for the REMOTE function and HAND key now controls for the LOCAL
function.
When MI is set to 56 for LOC/REM selection, if Pr.00-29 is set to 0, then the external terminal is
disabled.
When MI is set to 56 for LOC/REM selection, if Pr.00-29 is not set to 0, the external terminal has
the highest priority of command and the ATUO/HAND keys will be disabled.
Source of the Master Frequency Command(HAND)
Settings 0: Digital keypad
It is used to set the source of the master frequency in HAND mode.
Source of the Operation Command (HAND)
Settings 0: Digital keypad
It is used to set the source of the operation frequency in HAND mode.
Pr.00-20 and 00-21 are for the settings of frequency source and operation source in AUTO mode.
Pr.00-30 and 00-31 are for the settings of frequency source and operation source in HAND mode.
The AUTO/HAND mode can be switched by the keypad KPC-CC01 or multi-function input terminal
(MI).
The factory setting of frequency source or operation source is for AUTO mode. It will return to
AUTO mode whenever power on again after power off. If there is multi-function input terminal used
to switch AUTO/HAND mode. The highest priority is the multi-function input terminal. When the
Call 1(800)985-6929 for Sales
deltaacdrives.com
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
4~5: Reserved
5: Pulse input with direction command (Pr.10-16)
6: CANopen communication
7: Digital keypad potentiometer
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen communication
11-13