Delta C200 Series User Manual page 185

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
VFD015CB43A-21M
VFD015CB23A-21M
VFD015CB21A-20
VFD022CB21A-20
Stall Prevention Limit Level
Settings 0~100% (Refer to Pr.06-03, Pr.06-04)
When operation frequency is larger than Pr.01-01; e.g. Pr06-03=150%, Pr. 06-04=100% and Pr.
06-16=80%:
Calculate the Stall Prevention Level during acceleration: Pr.06-03 * Pr.06-16=150x80%=120%.
Calculate the Stall Prevention Level at constant speed: Pr.06-04 * Pr.06-16=100x80%=80%.
Present Fault Record
Second Most Recent Fault Record
Third Most Recent Fault Record
Fourth Most Recent Fault Record
Fifth Most Recent Fault Record
Sixth Most Recent Fault Record
Settings
0: No fault record
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during constant speed(ocn)
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration (LvA)
12: Low-voltage during deceleration (Lvd)
13: Low-voltage during constant speed (Lvn)
14: Stop mid-low voltage (LvS)
15: Phase loss protection (OrP)
16: IGBT over-heat (oH1)
17: Capacitance over-heat (oH2) (for 40hp above)
18: tH1o (TH1 open: IGBT over-heat
19: tH2o (TH2 open: capacitance over-heat
Call 1(800)985-6929 for Sales
Over-heating Level (℃)
100
100
100
100
protection error)
protection error)
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
95
VFD075CB43A-20
95
VFD040CB43A-21M
95
VFD055CB43A-21M
95
VFD075CB43A-21M
11-86
deltaacdrives.com
sales@deltaacdrives.com
Over-heating Level (℃)
100
100
100
100
Factory Setting: 50
sales@deltaacdrives.com
110
90
90
110

Advertisement

Table of Contents
loading

Table of Contents