Wiring precautions:
Reserves 5mm and properly install the wire into the terminal; fasten the installation by a
slotted screwdriver. If the wire is stripped, sort the wire before install into the terminal.
Flathead screwdriver: blade width 3.5mm, tip thickness 0.6mm
In the figure above, the factory setting for S1-SCM is short circuit. The factory setting for
+24V-COM is short circuit and SINK mode (NPN); please refer to Chapter 4 Wiring for more
detail.
Terminals
Digital control signal common
+24V
(Source)
Digital control signal common
COM
(Sink)
FWD
Forward-Stop command
REV
Reverse-Stop command
MI1
~
Multi-function input 1~6
MI6
MI7
~
Multi-function input 7~8
MI8
Multi-function relay output 1
RA1
(N.O.) a
Multi-function relay output 1
RB1
(N.C.) b
Multi-function relay common 1
RC1
Multi-function relay output 2
RA2
(N.O.) a
Multi-function relay common 2
RC2
Digital frequency meter 1
(when Pr.02-21=0, DFM1 is the setting of
DFM1
Pr.02-16)
(When Pr.02-21 ≧ 1, DM1 is the pulse output.)
Digital frequency meter 2
(When Pr.02-55 = 0, DFM2 is the setting value
DFM2
of Pr.02-17.)
(When Pr.02-55 ≧ 1, DFM2 is the pulse output)
DCM
Digital frequency signal common
Modbus RS-485
SG+
SG-
Call 1(800)985-6929 for Sales
Terminal Function
8
1
deltaacdrives.com
Chapter 6 Control Terminals|C200 Series
Factory Setting (NPN mode)
+24V±5% 100mA
Common for multi-function input terminals
FWD-DCM:
ON
forward running
OFF
deceleration to stop
REV-DCM:
ON
reverse running
OFF
deceleration to stop
Refer to parameters 02-01~02-08 to program the
multi-function inputs MI1~MI8.
ON: the activation current is 6.5mA 11Vdc
OFF: leakage current tolerance is 10μA 11Vdc
It can be a multi input option for Pr02-01 ~ 02-08. It
can also be used as a PG function. For more
information on PG function, see page 6-5.
Resistive Load:
5A(N.O.)/3A(N.C.) 250VAC
5A(N.O.)/3A(N.C.) 30VDC
Inductive Load (COS 0.4):
2.0A(N.O.)/1.2A(N.C.) 250VAC
2.0A(N.O.)/1.2A(N.C.) 30VDC
It is used to output each monitor signal, such as drive
is in operation, frequency attained or overload
indication.
The AC motor drive releases various monitor signals,
such as drive in operation, frequency attained and
overload indication, via transistor (open collector).
Regard the pulse voltage as the output monitor signal
Duty-cycle: 50%
Min. load impedance: 1kΩ/100pf
Max. current: 30mA
Max. voltage: 30Vdc
PIN4 、 PIN5 equals to the PIN4, PIN5 of the RJ45
internet cable connector.
PIN 3: GND
PIN 4: SG-
PIN 5: SG+
6-3
deltaacdrives.com
sales@deltaacdrives.com
DFM1
M ulti-function output
frequency term inals
30V/30m A 33kHz