Delta C200 Series User Manual page 167

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Settings 0.00~10.00V
Positive AUI Voltage Proportional Low Point
Settings 0.00~100.00%
Positive AUI Voltage Mid Point
Settings 0.00~10.00V
Positive AUI Voltage Proportional Mid Point
Settings 0.00~100.00%
Positive AUI Voltage High Point
Settings 0.00~10.00V
Positive AUI Voltage Proportional High Point
Settings 0.00~100.00%
When setting positive voltage AUI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency) and the motor runs in forward direction.
Three of the positive voltage AUI points can be set according to user's demand on voltage and
proportion, there is no setting limit for AUI points.
Negative AUI Voltage Low Point
Settings 0.00~-10.00V
Negative AUI Voltage Proportional Low Point
Settings 0.00~-100.00%
Negative AUI Voltage Mid Point
Settings 0.00~-10.00V
Negative AUI Voltage Proportional Mid Point
Settings 0.00~-100.00%
Negative AUI Voltage High Point
Settings 0.00~-10.00V
Negative AUI Voltage Proportional High Point
Settings 0.00~-100.00%
When setting negative voltage AUI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency) and the motor runs in reverse direction.
Call 1(800)985-6929 for Sales
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
11-68
deltaacdrives.com
sales@deltaacdrives.com
Factory Setting: 0.00
Factory Setting: 5.00
Factory Setting: 50.00
Factory Setting: 10.00
Factory Setting: 100.00
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: -5.00
Factory Setting: -50.00
Factory Setting: -10.00
Factory Setting: -100.00
sales@deltaacdrives.com

Advertisement

Table of Contents
loading

Table of Contents