460V Series
Frame Size
Model VFD-_ _ _CB43A-_ _ _
Applicable Motor Output (kW)
Applicable Motor Output (HP)
Rated Output Capacity (kVA)
Rated Output Current (A)
Overload Tolerance
Max. Output Frequency (Hz)
Carrier Frequency (kHz)
Rated Output Capacity (kVA)
Rated Output Current (A)
Overload Tolerance
Max. Output Frequency (Hz)
Carrier Frequency (kHz)
Input Current (A) Normal Duty
Input Current (A) Heavy Duty
Rated Voltage/Frequency
Operating Voltage Range
Frequency Tolerance
Cooling method
Braking Chopper
*1:_ _ _ " means models such as -20 / -21 / -21M.
General Specifications
Control Method
Starting Torque
Speed Response Ability
Torque Limit
Torque Accuracy
Max. Output Frequency (Hz) normal duty: 0.00~600.00Hz; Heavy duty: 0.00 ~ 600.00 Hz
Frequency Output Accuracy
Output Frequency
Resolution
Frequency Setting Signal
Accel./decel. Time
Main control function
Fan Control
Motor Protection
Over-current Protection
Over-voltage Protection
Over-temperature Protection Built-in temperature sensor
Stall Prevention
Grounding Leakage Current
Protection
Certifications
Call 1(800)985-6929 for Sales
deltaacdrives.com
*1
007
015
0.75
1.5
1
2.4
3.2
3.0
4.0
2.3
3.0
2.9
3.8
4.3
5.9
4.1
5.6
AC 380V~480V (-15% ~ +10%), 50/60Hz 3-Phase
Natural cooling
Reach up to 150% or above at 0.5Hz.
Under FOC+PG mode, starting torque can reach 150% at 0Hz.
5Hz (vector control can reach up to 40Hz)
Max. 200% torque current
±5%
Digital command:±0.01%, -10 ~+40
Digital command:0.01Hz, Analog command: 0.03 X max. output
frequency/60 Hz (±11 bit)
+10V~-10 , 0~+10V , 4~20mA , 0-20mA
0.00~600.00 seconds or 0.0~6000.0 seconds
Torque control, Droop control, Speed/torque control switching, Feed forward
control, Zero-servo control, Momentary power loss ride thru, Speed search,
Over-torque detection, Torque limit, 16-step speed (max), Accel/decel time
switch, S-curve accel/decel, 3-wire sequence, Auto-Tuning (rotational,
stationary), Dwell, Cooling fan on/off switch, Slip compensation, Torque
compensation, JOG
injection braking at start/stop, High slip braking, PID control (with sleep
function),Energy saving control, MODOBUS communication (RS-485 RJ45,
max. 115.2 kbps), Fault restart, Parameter copy
User Pr07-19 to control cooling fans.
Electronic thermal relay protection
For drive model 230V and 460V
Over-current protection for 240% rated current
current clamp 『 Normal duty: 170~175% 』 ; 『 Heavy duty: 180~185% 』
230: drive will stop when DC-BUS voltage exceeds 410V
460: drive will stop when DC-BUS voltage exceeds 820V
Stall prevention during acceleration, deceleration and running independently
Leakage current is higher than 50% of rated current of the AC motor drive
8-2
deltaacdrives.com
A0
022
037
2.2
3.7
2
3
5
4.8
7.2
6.0
9.0
rated output current is 120% for 60 seconds;
rated output current is 160% for 3 seconds
600.00Hz
2~15kHz (Factory Setting: 8 kHz)
4.5
6.5
5.7
8.1
rated output current is 150% for 60 seconds;
rated output current is 180% for 3 seconds
600.00Hz
2~15kHz (Factory Setting: 2 kHz)
8.7
14
8.3
13
323~528Vac
47~63Hz
Built-in
1: V/F, 2: SVC, 3: VF+PG, 4: FOC+PG,
℃, Analog command: ±0.1%, 25±10℃
frequency,
Frequency upper/lower limit settings, DC
GB/T12668-2
sales@deltaacdrives.com
A
040
055
075
4.0
5.5
7.5
5.5
7.5
8.4
10
10.5
12
7.6
9.6
9.5
11
15.5
17
14.5
16
Fan cooling
sales@deltaacdrives.com
10
14
18
14
17
20
19

Advertisement