14.4.3 The Edition of PLC Ladder Diagram
The program edited method is from left power line to right power line. (The right power line will
be omitted during the edited of WPLSoft.) After editing a row, go to editing the next row. The
maximum contacts in a row are 11 contacts. If you need more than 11 contacts, you could have
the new row and start with continuous line to continue more input devices. The continuous
number will be produced automatically and the same input point can be used repeatedly. The
drawing is shown as follows.
X0
00000
The operation of ladder diagram is to scan from left upper corner to right lower corner. The
output handling, including the operation frame of coil and application command, at the most
right side in ladder diagram.
Take the following diagram for example; we analyze the process step by step. The number at
the right corner is the explanation order.
X0
M0
X3
The explanation of command order:
1
2
OR
3
AND
4
Call 1(800)985-6929 for Sales
Block in parallel
Multiple output
Output command of coil
drive
Basic command,
Application command
Inverse logic
X1
X2
X3
X4
X11 X12 X13
Row Number
X1
Y1
T0
M1
LD
X0
M0
X1
LD
X3
deltaacdrives.com
ORB
MPS
MRD
MPP
OUT
Basic command/
Application
command
INV
X5
X6
X7 X10 C0
X4
M3
14-12
deltaacdrives.com
sales@deltaacdrives.com
Chapter 14 PLC Function |C200 Series
none
none
Y, M
none
C1
00000
Y0
Y1
TMR
T0
K10
sales@deltaacdrives.com