Delta C200 Series User Manual page 163

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
It is used to adjust the analog voltage level (Pr.03-20) that terminal AFM outputs.
This parameter is set the corresponding voltage of the analog output 0.
Analog Output 1 when in REV Direction (AFM1)
Analog Output 2 when in REV Direction (AFM2)
Settings 0: Absolute value in REV direction
Reserved
Reserved
AVI Selection
Settings 0: 0-10V
ACI Selection
Settings 0: 4-20mA
When changing the input mode, please check if the switch of external terminal (SW3, SW4)
corresponds to the setting of Pr.03-28~03-29.
Status of PLC Output Terminal
Settings 0~65535
P.03-30 shows the external multi-function output terminal that used by PLC.
Call 1(800)985-6929 for Sales
deltaacdrives.com
1: Output 0V in REV direction; output 0-10V in FWD direction
2: Output 5-0V in REV direction; output 5-10V in FWD direction
10V( 20mA)
03-18
03-21
0V
03-24
( 0mA)
03-22=0
03-25=0
Selections for the analog output dir ec ti on
1: 0-20mA
2: 4-20mA
1: 0-10V
2: 0-20mA
Monitor the status of PLC analog output terminals
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
10V( 20mA)
F requenc y
0V
( 0mA)
03-22=1
03-25=1
11-64
sales@deltaacdrives.com
Factory Setting: 0
10V( 20mA)
F requenc y
5V
( 12mA)
03-22=2
03-25=2
Factory Setting: 0
Factory Setting: 0
Factory Setting: ##
sales@deltaacdrives.com