Delta C200 Series User Manual page 7

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Chapter 1 Introduction|C200 Series
3.
The gap discharge may occur when the transient voltage is higher than 1,000V. Besides,
electro-magnetic compatibility of the AC motor drives will be lower after cutting the RFI jumper.
4.
Do NOT cut the RFI jumper when main power is connected to earth.
5.
The RFI jumper cannot be cut when Hi-pot tests are performed. The mains power and motor must be
separated if high voltage test is performed and the leakage currents are too high.
6.
To prevent drive damage, the RFI jumper connected to ground shall be cut off if the AC motor drive is
installed on an ungrounded power system or a high resistance-grounded (over 30 ohms) power
system or a corner grounded TN system.
Call 1(800)985-6929 for Sales
deltaacdrives.com
1-4
deltaacdrives.com
sales@deltaacdrives.com
sales@deltaacdrives.com

Advertisement

Table of Contents
loading

Table of Contents