Delta C200 Series User Manual page 225

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Content
Command
Write only
Status monitor
Read only
Call 1(800)985-6929 for Sales
deltaacdrives.com
Chapter 11 Description of Parameter Settings|C200 Series
Address
00B: No function
01B: FWD
Bit 4-5
10B: REV
11B: Change direction
00B: 1st accel/decel
01B: 2nd accel/decel
Bit 6-7
10B: 3rd accel/decel
11B: 4th accel/decel
Bit 8-11
000B: master speed
0001B: 1st accel/decel.
0010B: 2nd accel/decel
0011B: 3rd accel/decel
0100B: 4th accel/decel
0101B: 5th accel/decel
0110B: 6th accel/decel
0111B: 7th accel/decel
1000B: 8th accel/decel
1001B: 9th accel/decel
1010B: 10th accel/decel
1011B: 11th accel/decel
1100B: 12th accel/decel
1101B: 13th accel/decel
1110B: 14th accel/decel
1111B: 15th accel/decel
Bit 12
1: enable bit06-11 function
Bit 13~14 00B: No function
01B: operated by digital keypad
10B: operated by Pr.00-21 setting
11B: change operation source
Bit 15
Reserved
2001H
Frequency command
Bit 0
1: EF (external fault) on
Bit 1
1: Reset
2002H
Bit 2
1: B.B. ON
Bit 3-15
Reserved
Error code: refer to Pr.06-17 to Pr.06-22
2100H
AC Drive Operation Status
2101H
Bit0
00b: Drive stops
01b: Drive decelerating
Bit1
10b: Drive standby
11b: Drive operating
Bit2
1: JOG Command
Operation Direction
Bit3
00b: FWD run
01b: from REV run to FWD run
Bit4
10b: REV run
11b: from FWD run to REV run
1: Master frequency controlled by communication
Bit8
Bit9
1: Master frequency controlled by analog signal
1: Operation command controlled by
Bit10
Bit11
1: Parameter locked
Bit12
1: Enable to copy parameters from keypad
Bit13~15
Reserved
2102H
Frequency command (F)
11-126
deltaacdrives.com
Function
interface
communication interface
sales@deltaacdrives.com
sales@deltaacdrives.com

Advertisement

Table of Contents
loading

Table of Contents