Delta C200 Series User Manual page 254

Intelligent vector control drive
Table of Contents

Advertisement

Call 1(800)985-6929 for Sales
Display on
KPE-LE02
Fault
Oc HW error
Fault
Ov HW error
Fault
occ HW error
Fault
Auto tuning err
Fault
PID Fbk error
Fault
PG Fbk error
Fault
PG Fbk loss
Fault
PG Fbk over SPD
Fault
PG Fbk deviate
Fault
PG Ref error
Fault
PG Ref loss
Call 1(800)985-6929 for Sales
deltaacdrives.com
Display on
KPC-CC01
OC hardware error
Corrective Actions:
Hd1
Re-power on to try it. If fault code is still displayed on the keypad, please
return to the factory.
OV hardware error
Corrective Actions:
Hd2
Re-power on to try it. If fault code is still displayed on the keypad, please
return to the factory.
Occ hardware error
Corrective Actions:
Hd3
Reboots the power. If fault code is still displayed on the keypad please
return to the factory
Auto tuning error
Corrective Actions:
AUE
1. Check cabling between drive and motor
2. Check the motor capacity and parameters settings
3. Retry again
PID loss (ACI)
Corrective Actions:
AFE
1.
Check the wiring of the PID feedback
2.
Check the PID parameters settings
PG feedback error
PGF1
Corrective Actions:
Check if Pr.10-01 is not set to 0 when it is PG feedback control
PG feedback loss
PGF2
Corrective Actions:
Check the wiring of the PG feedback
PG feedback stall
Corrective Actions:
PGF3
1.
Check the wiring of the PG feedback
2.
Check if the setting of PI gain and deceleration is suitable
3.
Return to the factory
PG slip error
Corrective Actions:
PGF4
1.
Check the wiring of the PG feedback
2.
Check if the setting of PI gain and deceleration is suitable
3.
Return to the factory
Pulse input error
Corrective Actions:
PGr1
1.
Check the pulse wiring
2.
Return to the factory
Pulse input loss
Corrective Actions:
PGr2
1. Check the pulse wiring
2. Return to the factory
deltaacdrives.com