Chapter 6 Control Terminals|C200 Series
Terminals
Potentiometer power supply
+10V
Analog voltage input
AVI
Analog current input
ACI
Auxiliary analog voltage input
AUI
AFM1
AFM2
ACM
Analog Signal Common
Analog input terminals (AVI, ACI, AUI, ACM)
Analog input signals are easily affected by external noise. Use shielded wiring and keep it as
short as possible (<20m) with proper grounding. If the noise is inductive, connecting the shield to
terminal ACM can bring improvement.
If the analog input signals are affected by noise from the AC motor drive, please connect a
capacitor and ferrite core as indicated in the following diagram.
Call 1(800)985-6929 for Sales
deltaacdrives.com
Terminal Function
+10V AVI circuit
AVI
ACM
internal circuit
ACI
ACI circuit
internal circuit
ACM
+10
AUI circuit
AUI
ACM
internal circuit
NOTE: Wire size of analog control signals: 18 AWG (0.75 mm
deltaacdrives.com
Factory Setting (NPN mode)
Analog frequency setting: +10Vdc 20mA
Impedance: 20kΩ
Range: 0~10V/0~20mA/ 4~20mA(Pr.03-38)
=0~Max. Output Frequency (Pr.01-00)
AVI switch, factory setting is 0~10V
0-20mA
ON
4-20mA
1
0-10V
2
ACI
Impedance: 500Ω
Range: 4~20mA/0~10V/0~20mA(Pr.03-39)
=0~Max. Output Frequency (Pr.01-00)
ACI Switch, factory setting is 4~20mA
0-20mA
ON
4-20mA
2
0-10V
1
ACI
Impedance: 20kΩ
Range: -10~+10VDC=0 ~ Max. Output
Frequency(Pr.01-00)
Impedance: 100kΩ (voltage output)
Output current: 2mA max
Resolution: 0~10V corresponds to Max. operation
frequency
Range: 0~10V
Impedance: 100Ω (current output)
Output current: 20mA max
Resolution: 0~20mA corresponds to Max. operation
frequency
Range: 0~20mA, 4~20mA
Common for analog terminals
6-4
sales@deltaacdrives.com
2
) with shielded wire